Backup Lugs

Component Wire Gauge 1 Tool Size Wire Strip Length Torque
A Backup Terminals on Internal Panelboard 6 AWG – 250 kcmil 5/16-inch hex 1 ¼-inch (32 mm) 275 in-lb, 23 ft-lb
B Backup Terminals (1x) #4 AWG - 250 kcmil, or

(2x) #4 AWG - 4/0 stranded2

3/8-inch hex 1 ¼-inch (32 mm) 250 in-lb, 21 ft-lb
C Internal panelboard jumper bridge N/A 7/16-inch hex N/A (2) Factory-installed 7/16" bolts, 80 in-lb (9 N-m)

1 Use copper or aluminum conductors rated to a minimum of 75°C.

2 Conductors must be the same size and material when terminating more than one conductor under these terminals.

Note
The internal panelboard jumper bridge replaces the pre-bent jumper conductors that were used to supply power to the internal panelboard in previous generations of the Tesla Gateway.