| 1 |
Tesla Asset Controller
(TACO) |
Functions as site controller (used for commissioning, logging,
site control, and other site-level features). Connects to Universal
Wall Connector with 4-conductor communication cable. |
| 2 |
Neutral Balancing
Transformer |
Provides Neutral when off-grid for a 120/240V split phase
system. |
| 3 |
Islanding contactor
connector |
Connects the islanding contactor to the TACO with a
factory-installed harness. |
| 4 |
Internal panelboard |
Factory-installed 8/16 panelboard connected to Backup terminals
with a removable bridge jumper. Includes hold-down accessory kit for
backfed breakers; compatible with Siemens QP, Eaton BR, and SquareD
HOM series breakers. |
| 5 |
Supply lugs |
Factory-installed L1 and L2 lugs for incoming power supply. Lugs
can be removed and replaced with an optional main breaker. |
| 6 |
Neutral terminals |
Three large neutral lugs and one neutral bar for multiple smaller
wires. |
| 7 |
Backup terminals |
L1 and L2 connections for a load center that is being backed up.
Lugs are rated for double-lugging two conductors of the same size.
See Powershare Gateway Wiring for wiring specifications. |
| 8 |
Neutral-ground bonding
screw |
Factory-installed screw that bonds neutral to ground. Removable
for different equipment configurations. |
| 9 |
Ground terminals |
Four large ground lugs and one ground bar for multiple smaller
wires. |