Required Supplies

  • Powershare Gateway mounting hardware
  • Conduit adapters (necessary for cable entry into Powershare Gateway)
  • Conduit or raceway (depending on local electrical requirements)
  • Minimum 600 V rated copper cable for power connections to Wall Connector and Powershare Gateway
    Note
    For maximum power, check the temperature rating of circuit breaker used for Universal Wall Connector:
    • For 60°C rated circuit breaker, use minimum 4 AWG, 90°C THWN-2-rated copper wire for conductors.
    • For 75°C rated circuit breaker, use minimum 6 AWG, 90°C THWN-2-rated copper wire for conductors.
    Increase conductor size if necessary.
  • Minimum 300 V 4-conductor twisted pair cable (18 - 16 AWG) for communication between:
    • Powershare Gateway and Backup Switch
    • Powershare Gateway and Universal Wall Connector
      Note
      Two cables can be used for communication between Powershare Gateway and Universal Wall Connector.
  • If the system includes solar in the backup circuit, warning label for main electrical panel (see Close Equipment and Turn System On for example label)