Required Supplies
- Powershare Gateway mounting hardware
- Conduit adapters (necessary for cable entry into Powershare Gateway)
- Conduit or raceway (depending on local electrical requirements)
- Minimum 600 V
rated copper cable for power connections to Wall
Connector and Powershare GatewayNoteFor maximum power, check the temperature rating of circuit breaker used for Universal Wall Connector:
- For 60°C rated circuit breaker, use minimum 4 AWG, 90°C THWN-2-rated copper wire for conductors.
- For 75°C rated circuit breaker, use minimum 6 AWG, 90°C THWN-2-rated copper wire for conductors.
- Minimum 600 V
4-conductor twisted pair cable (18 - 16 AWG) for
communication between:
- Powershare Gateway and Backup Switch
- Powershare Gateway
and Universal Wall ConnectorNoteTwo cables can be used for communication between Powershare Gateway and Universal Wall Connector.
- If the system includes solar in the backup circuit, warning label for main electrical panel (see Close Equipment and Turn System On for example label)