Required Supplies

  • Powershare Gateway mounting hardware
  • Conduit adapters (necessary for cable entry into Powershare Gateway)
  • Conduit or raceway (depending on local electrical requirements)
  • Minimum 600 V rated copper cable for power connections to Wall Connector and Powershare Gateway
    Informational PurposesAn informational icon, calling your attention
    Note
    For maximum power, check the temperature rating of circuit breaker used for Universal Wall Connector:
    • For 60°C rated circuit breaker, use minimum 4 AWG, 90°C THWN-2-rated copper wire for conductors.
    • For 75°C rated circuit breaker, use minimum 6 AWG, 90°C THWN-2-rated copper wire for conductors.
    Increase conductor size if necessary.
  • Minimum 600 V 4-conductor twisted pair cable (18 - 16 AWG) for communication between:
    • Powershare Gateway and Backup Switch
    • Powershare Gateway and Universal Wall Connector
      Informational PurposesAn informational icon, calling your attention
      Note
      Two cables can be used for communication between Powershare Gateway and Universal Wall Connector.
  • If the system includes solar in the backup circuit, warning label for main electrical panel (see Close Equipment and Turn System On for example label)