Make Powershare Gateway Supply Connections
- Connect the supply conductors to the Powershare Gateway Supply terminals or main breaker terminals.
- Connect the supply Neutral to a main Neutral terminal on the Grid side.
- Connect the supply Ground to a main Ground terminal.
Note
When an Eaton main breaker is
installed, S1 and S2 are swapped.
Component | Recommended Wire Color | Wire Gauge 1 | Tool Size | Wire Strip Length | Torque |
---|---|---|---|---|---|
Supply Terminals | Black, Red | 6 AWG – 250 kcmil | 5/16-inch hex | 1 ¼-inch (32 mm) | 275 in-lb, 23 ft-lb |
Main Neutral Terminals | White | (1x) #4 AWG - 250 kcmil | 3/8-inch hex | 1 ¼-inch (32 mm) | 250 in-lb, 21 ft-lb |
(2x) #4 AWG - 4/0 stranded2, 3 | |||||
Main Ground Terminals | Green or Bare | 6 AWG – 2/0 | 3/16-inch hex | ¾-inch (20 mm) | 120 in-lb, 10 ft-lb |
1 Use copper or aluminum conductors rated to a minimum of 75°C.
2 Conductors must be the same size and material when terminating more than one conductor under these terminals.
3Double lugging is allowed only when conductors are paralleled (part of the same circuit) to increase ampacity for a single circuit.
CAUTION
Do not modify the
factory lug configuration.