Prepare Wirebox for Conduit Fittings
The default conduit size is 3/4 in (21 mm). 1 in (27 mm) conduit is acceptable if needed. Ensure that the conduit hub used are rated Type 3R.
- For top or bottom entry: Manually remove the conduit plug.
- For rear entry: Drill with 1-1/8 in (29 mm) step bit to prepare wirebox for fittings.
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
---|---|---|---|
![]() | ![]() | ![]() | ![]() |
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
---|---|---|---|
Do not expand. | ![]() ![]() | ![]() | ![]() |
Note
For 1 in (27 mm) rear and
bottom entry options, drill with 1-3/8 in (35 mm) step bit to prepare wirebox for
fittings.