Negative Site Reading
On the landing page, the site value is negative. An alert will appear on the landing page
Steps to Troubleshoot
- Confirm the CTs are facing
the correct way:
- Locate the CT(s) used to measure the source that is displaying incorrect power flow readings.
- Verify the CT(s) are oriented such that the label is facing toward the source (away from the breaker).
- Confirm the CTs are measuring
the correct phase:
- Locate the CT on the Meter page in the Device Setup interface in Tesla One.
- Determine which phase the CT should be measuring.
- Verify the CT is measuring the correct phase.
Note
The site value can be negative
if power is flowing to the grid.