Powerwall / Powerwall+ is Discharging at Full Power
Powerwall / Powerwall+ is discharging at its maximum discharge, and the site reading increases as Powerwall / Powerwall+ discharges
Steps to Troubleshoot
- If using external Site CTs:
- Confirm the CTs are
facing the correct way:
- Locate the CT(s) used to measure the source that is displaying incorrect power flow readings.
- Verify the CT(s) are oriented such
that the label is facing toward the source (away from the breaker).
- Solar Current Transformer: Label toward the Inverter
- Site Current Transformer: Label toward the Grid
- Confirm the CTs are
measuring the correct phase:
- Locate the CT on the Meter page in Tesla One.
- Determine which phase the CT should
be measuring.NoteIf using Gateway CTs, the ports are CT 1 (Line 1), CT2, (Line 2), CT 3 (defaults to Line 1 but can be configured as Line 2 in Tesla One).NoteIf using a Neurio meter, the ports are A (Line 1), B (Line 2), B (Line 2), A (Line 1) and are determined by voltage reference.
- Verify the CT is measuring the
correct phase. NoteIn the examples above, the CT is monitoring a solar inverter conductor, which is why only (1) CT is required.
- Confirm the CTs are
facing the correct way:
- For systems with Backup Gateway 2, verify the supply conductors feeding the Gateway are connected to the Supply terminals:
- Verify any backup conductors are connected to the Backup terminals (or the internal panelboard if it is connected to the Backup terminals):
- Follow the steps in Gateway CTs and Neurio CTs are Overlapping to ensure site and solar loads are monitored only once, and the Powerwall conductors are not captured.