Locate the CT(s) used to measure the source that is displaying incorrect power flow
readings.
Verify the CT(s) are oriented such
that the label is facing toward the source (away from the breaker).
Solar Current Transformer:
Label toward the inverter
Site Current Transformer:
Label toward the Grid Figure 1. Tesla 100 A CT
(for Backup Gateway 2) Orientation in Relation to Power FlowFigure 2. Neurio W2 CT
Correctly Oriented to Measure Solar (top) and Incorrectly Oriented
(bottom)