The Powerwall+ / Tesla
Solar Inverter is failing the MCI self-test.
Note
If a string displays voltage during
the self-tests but is grayed out and displaying 0V after self-tests have completed,
there is likely an MCI issue. See MCI Diode Test and Resistance Test (MCI Health Tests) to identify
faulty MCI(s).
Confirm MCIs are Functioning as
Expected
Confirm the MPPTs are functioning properly:
Set the inverter state to DC Only mode.
Confirm each string displays the
expected voltage as displayed on the planset.Figure 1. Tesla Solar Inverter /
Powerwall+ Expected Voltage in
Device Setup Interface
If a string is not displaying the
expected voltage:
Select Stop System on
the landing page in Tesla One, then turn Powerwall+ / Tesla
Solar Inverter OFF.
Disconnect a functional
string (displays the correct voltage and amperage when the system is
running) from its MPPT (consider this a functional MPPT).
Disconnect the
problematic string from its MPPT, then connect the problematic string to
the functional MPPT.
Turn the system back ON
and Start System
and Enable Solar.
If the problematic string
now displays the correct voltage and amperage (while plugged in to the
functional MPPT), contact Tesla Support for additional troubleshooting
support.
Note
Move
the string back to its original (presumed faulty) MPPT to confirm
that MPPT still does not function. If, upon moving back to the
original MPPT, the string displays the correct voltage, the issue is
resolved. No additional action is required.
If the string does not display
the expected voltage while plugged into the new MPPT, see MCI Diode Test and Resistance Test (MCI Health Tests) for
instructions to test all MCIs in the failing string. If a faulty MCI is
identified, replace it.
If all strings are failing the MCI self-test, contact Install Support for additional
troubleshooting support.