MCI Diode Test and
Resistance Test (MCI Health Tests)
The following tests are used to confirm MCIs are functioning as expected.
Before removing MCIs from an
array to test them, confirm MCIs have been installed per the Powerwall+ / Tesla
Solar Inverter installation manual to
comply with RSD code requirements (1 MCI per every X modules, or 1 MCI on ends
of strings, depending on the system being installed, see manual for details).
When identifying which MCI(s) are
faulty, remove all MCIs from the array and perform the MCI health tests listed
below. Replace any faulty MCI with a known healthy MCI when installing the MCIs
in the array again.
CAUTION
If an array has faulty MCI(s)
and there are not sufficient healthy MCIs to replace them, ensure the system
is left OFF until the return visit has been completed and the required
number of MCIs has been installed.
Note
Take photos of all readings while troubleshooting.
Tesla installers: Upload these screenshots to the JCO in the Tesla One app
If Install Support is required, they will use these screenshots to verify the
steps that have been completed and can be skipped during the call.
MCI Diode
Test
The MCI diode test is used to ensure the diode in the MCI is functioning as
expected.
To perform a diode test:
Connect the red lead of a
digital multimeter to the MC4+ lead of an MCI.
Connect the black lead of the
digital multimeter to the MC4- lead of the MCI.
Turn the dial on the
multimeter to the Ohm symbol, then push the SEL button twice to
enter Diode testing mode. The Diode test symbol will appear on the display.
Review the reading on the
digital multimeter. It should be approximately 0.5V.
A reading greater
than 1V means the MCI failed open.
A reading less than
0.3V means the MCI failed short.
A reading of 'OL'
indicates there is a missed connection or FET solder joint in the
MCI.
If a suspected non-functional MCI is found in the field, confirm the MCI is the issue
by swapping out the MCI and verifying the issue has been fixed. Swap the original
unit back in again to see if the issue remains fixed, or if the issue occurs again
with the original MCI installed.
Note
Avoid excessive stress to wires when performing the diode test. Faulty connection
of press fit pins will result in an 'OL' reading the multimeter. If this occurs,
manipulate the wires and measure again. For an optional additional check, if the
diode test initially failed and now passes, try it again to see if wire management
did indeed fix the issue.
MCI
Resistance Test
To perform an MCI resistance test:
Connect the red lead of a
digital multimeter to the MC4- lead of an MCI.
Connect the black lead of the
digital multimeter to the MC4+ lead of the MCI.
Turn the dial on the multimeter to the Ohm symbol, then push the SEL
button once to enter Resistance testing mode. The Resistance test symbol
will appear on the display.
Review the reading on the
digital multimeter. It should read 'OL'.
Figure 1. MCI Resistance Test with
Digital Multimeter
Perform a visual inspection of the MCI, looking for deformation, physical damage,
and/or damage to connector integrity. If any issues are found during the visual
inspection, or if the MCI fails the resistance test, replace the MCI.